Online UPS systems for networks and data centres
– On-line double conversion UPS technology for high availability
– n+x technology for redundancy or power increase
– RS232 communication interface
– Communication slot for expansion cards
– Battery systems with a service life expectancy of 10-12 years according to EUROBAT
– DSP and CAN-bus system for high reliability
– max. efficiency through the use of high-frequency IGBT technology

– Type Power: 15 kVA/10.5kW

UPS INPUT
– Rated connected voltage: 400/230 Vac
– Voltage range without battery mode: 304-478 Vac (Bypass: 176-261 Vac)
– Frequency (auto selection): 50/60 Hz +/- 4 Hz
– Powerfactor: > 0.95
– Current consumption max.: 19A / 68A (bypass)

UPS OUTPUT
– Rated AC voltage (single-phase): 220 Vac / 230 Vac / 240 Vac +/- 1%
– Frequency in battery mode: 50/60 Hz +/- 0.1% (slew rate 1Hz/s)
– Output current (at 230 Vac): 43.4 A
– Transfer time at mains failure: 0 ms (zero transfer)
– Voltage wave form: Sinusoidal, THD < 2% - Overload response: 130% for 10 min. / > 130% for 1 s (automatic transfer to bypass mode – zero transfer)
– Crast factor for non-linear load: 3:1
– Short / deep discharge protection: Yes

BATTERY
– Rated Voltage: 240 Vdc
– Load characteristic: IU – characteristic curve (charging voltage 274 Vdc/charging current max. 4.2 Adc)
– Autonomy time: Runtime extension with scalable external battery packs
– Overload / Deep discharge protection: Yes

COMMUNICATION
– Interface: RS232 with status message and measured values (Communications-Slot – Potencial-free contacts, USB, SNMP)
– Shutdown software (on CD): Included for common Operating Systems (Windows, Linux, Mac) (Single licence "CompuWatch" with a 5 fold network licence)
– Alarms (audible/optical): LED bar graph showing UPS load, battery capacity, indicators for mains failure, overload, battery low, battery replacement, fault

GENERAL DATA
– Efficiency total AC-AC (at full load): > 90%
– Noise level (1m distance): =< 60 dBA - Operating temperature: 0 - 40C - Installation height: Up to 1000m above sea level, at nominal load - Humidity: 0 - 95% (non condensing) - Dimensions (W×H×D): 260×720×570 mm - Weight: 55 kg